APSU PVs
The APS-U has changed many of the process variables(PVs) used for the last 25 years. This includes PVs related to EPS (or FEEPS), PSS, status, insertion devices, etc. Sometimes only the PV name has changed but in some instances the old PV does not have a direct replacement.
This wiki will help to describe what is new, what has been removed, and how to convert to using some of the new PVs available.
All APS-U PVs
All of the PVs currently served by the APS-U are listed in the files in the directory /APSshare/C2/iocinfo/pvdata/. This is an rsync of the oxygen-based directory /net/helios/C2/iocinfo/pvdata/. The files located in this directory are named after the IOC which hosts those PVs. By grepping through the files, one can determine if a PV exists or if the name has changed.
% grep -s XFD:srCurrent /APSshare/C2/iocinfo/pvdata/* /APSshare/C2/iocinfo/pvdata/siocblops:XFD:srCurrent
A useful tool located in /APSshare/bin called 'pvExist' will also confirm whether a PV is valid and what IOC is hosting it:
% /APSshare/bin/pvExist XFD:srCurrent Using IOC_INFO environment variable /APSshare/C2/iocinfo siocblops:XFD:srCurrent % /APShare/bin/pvExist XFD:srCurrent1 Using IOC_INFO environment variable /APSshare/C2/iocinfo XFD:srCurrent1 not found
EPS (or FEEPS) PVs
Here are the Equipment Protection System PVs for APS-U. Compare to the old PVs as described at https://epics.anl.gov/bcda/aps/frontendpvs.php
Note that there are not 'xx' or 'yy' display subs - only 'Z' and 'a') In other words, display substitution is Z=Sxxyy, a=SxxyyFE where:
xx = 2 digit sector number yy = BM or ID
Changed
Old PV Name: New PV Name: EPS:xx:yy:PS1:POSITION Sxxyy-FEEPS:PS1:PositionM 0 Moving 1 Closed 3 Open 4 Position Error
EPS:xx:yy:PS2:POSITION Sxxyy-FEEPS:PS2:PositionM 0 Moving 1 Closed 3 Open 4 Position Error
EPS:xx:yy:SS1:POSITION Sxxyy-FEEPS:SS1:PositionM 0 Moving 1 Closed 3 Open 4 Position Error
EPS:xx:yy:SS2:POSITION Sxxyy-FEEPS:SS2:PositionM 0 Moving 1 Closed 3 Open 4 Position Error
EPS:xx:yy:FEV:POSITION Sxxyy-FEEPS:FEV:PositionM 0 Moving 1 Closed 3 Open 4 Position Error
EPS:xx:yy:BIV:POSITION Sxxyy-FEEPS:BIV:PositionM 0 Moving 1 Closed 3 Open 4 Position Error
New
These PVs are new and were not present before:
Sxxyy-FEEPS:TripsExistM 0 OFF (No Trip) 1 ON (Trip(s) Exist)
Sxxyy-FEEPS:FaultsExistM 0 OFF (No Fault) 1 ON (Fault(s) Exist)
Sxxyy-FEEPS:WarningsExistM 0 OFF (No Warning) 1 ON (Warning(s) Exist)
Sxxyy-FEEPS:ShutterPermitWarnM 0 OFF (No Warning from BLEPS) 1 ON (Warning(s) Exist from BLEPS)
Sxxyy-FEEPS:VacuumPermitWarnM 0 OFF (No Warning from BLEPS) 1 ON (Warning(s) Exist from BLEPS)
Removed
The following PVs have been removed and there is no replacement:
EPS:xx:yy:PS1:STATUS EPS:xx:yy:PS2:STATUS EPS:xx:yy:SS1:STATUS EPS:xx:yy:SS2:STATUS EPS:xx:yy:SV:STATUS EPS:xx:yy:SV:POSITION EPS:xx:yy:FV:STATUS EPS:xx:yy:FV:POSITION EPS:xx:yy:FEV:STATUS EPS:xx:yy:BIV:STATUS EPS:xx:yy:CC1:RDY EPS:xx:yy:CC2:RDY EPS:xx:yy:VAC:CC1:RDY EPS:xx:yy:VAC:CC2:RDY EPS:xx:yy:MM:F
PSS PVs
There have been a significant amount of PV changes with the PSS PVs. Unfortunately there is no easy translation tool from older PVs to the new APSU PSS PVs.
Each beamline could look at the PSS Input/Output EPICS screens to determine what their new PVs are. This can be done by starting up /APSshare/adlsys/xfd-display then selecting the light blue PSS button, then selecting the drop-down blue button for the beamline (e.g. 27-ID). From there select either "Inputs" or "Outputs". If the beamline is a Gen4 system, then select either "Systems" or "Stations". These 2 EPICS screens will display all of the PSS PVs and you can find the appropriate ones needed.
According to the SI group, for Gen3 PSS system the shutter control PVs did not change. Only the Gen4 systems PVs were changed. For this second run in 2024, the Gen4 systems will be 8ID, 9ID, 15ID, 16BM, 19ID, 20ID, 22ID, 25ID (to be completed after the Aug 2024 shutdown), 31ID, 33ID and 34ID. See the following example PSS Gen4 PVs where:
xx = 2 digit sector number yy = BM or ID Old Gen PSS PV's New Gen4 PSS PV's PA:xxyy:STA_A_FES_OPEN_PL Sxxyy-PSS:FES:BeamBlockingM PA:xxyy:STA_D_SDS_OPEN_PLS Sxxyy-PSS:SDS:BeamBlockingM PA:xxyy:STA_A_SEARCHED_PL Sxxyy-PSS:StaA:SecureM PA:xxyy:STA_C_SEARCHED_PL Sxxyy-PSS:StaC:SecureM PA:xxyy:STA_D_SEARCHED_PL Sxxyy-PSS:StaD:SecureM
APS Status PVs
The following describes the status PVs. These can be compared to the previous PVs which are explained at https://epics.anl.gov/bcda/aps/statuspvs.php
Changed
S:DesiredMode 0 State Unknown 1 USER OPERATIONS 2 SUPLEMENTAL TIME 3 Not Used 4 ASD Studies 5 NO BEAM 6 MAINTENANCE S:ActualMode 0 State Unknown 1 NO BEAM 2 Injecting 3 Stored Beam 4 Delivered Beam 5 MAINTENANCE
OLD PV NEW PV ACIS:ShutterPermit RF-ACIS:FePermit:Sect1To35IdM (1-35 Beamlines) RF-ACIS:FePermit:35Bm38AmM (35BM and 38AM Beamlines) ACIS:ShutterPermit XFD:ShutterPermit (alias to RF-ACIS:FePermit:Sect1To35IdM) S:SRcurrentAI XFD:srCurrent
Unchanged
S:OrbitCorrection:CC S:OrbitControlLawXFineBO S:OrbitControlLawYFineBO S:FillNumber XFD:srCurrent S:SRtimeCP & S:SRcurrentCP S:SRdateCP XFD:LifeTimeHrs XFD:message1 XFD:message2 XFD:message3 XFD:message4 XFD:message5 XFD:message6 XFD:message14 XFD:message15 XFD:message17 XFD:message18 OPS:TimeOfDaySI Liquid Nitrogen Distribution System Information PVs
Removed
SRFB:GBL:LoopStatusBI SRFB:GBL:VLoopStatusBI SRFB:GBL:HLoopStatusBI SRFB:dsp2:xRMSmotion30HzPkM SRFB:dsp2:yRMSmotion30HzPkM S:VID1:filteredXemittance S:VID1:filteredYemittance S:VID1:filteredCoupling ALL TopUp related information PVs
Insertion Device PVs
Here is a list of old and new PV names for insertion devices. The names have changed but there is no change to their meanings.
Note that there is no sector 4 CPU and the messages for the message PVs are still the same as well.
Compare this to the previous page at https://epics.anl.gov/bcda/aps/idpvs.php
$(xx) = 2 digit sector number $(yy) = US or DS (Position of ID in storage ring straight) (Note: there are not any xx or yy display subs, display substitution is P=SxxID:yyID)
Changed
Control Process Variables
Old PV Name: New PV Name: ID$(xx):GapSet S$(xx)ID:$(yy)ID:GapSetC ID$(xx):TaperGapSet S$(xx)ID:$(yy)ID:TaperGapSetC ID$(xx):ScanGap S$(xx)ID:$(yy)ID:ScanGapC ID$(xx):ScanEnergy S$(xx)ID:$(yy)ID:ScanEnergyC ID$(xx):EnergySet S$(xx)ID:$(yy)ID:EnergySetC ID$(xx):TaperEnergySet S$(xx)ID:$(yy)ID:TaperEnergySetC ID$(xx):DeadbandGap S$(xx)ID:$(yy)ID:DeadbandGapC ID$(xx):HarmonicValue S$(xx)ID:$(yy)ID:HarmonicValueC ID$(xx):Start S$(xx)ID:$(yy)ID:StartC ID$(xx):Stop S$(xx)ID:$(yy)ID:StopC
Monitor Process Variables
ID$(xx):Gap S$(xx)ID:$(yy)ID:GapM ID$(xx):TaperGap S$(xx)ID:$(yy)ID:TaperGapM ID$(xx):Energy S$(xx)ID:$(yy)ID:EnergyM ID$(xx):TaperEnergy S$(xx)ID:$(yy)ID:TaperEnergyM ID$(xx):Busy S$(xx)ID:$(yy)ID:BusyM ID$(xx):Message1 S$(xx)ID:$(yy)ID:Message1M ID$(xx):Message2 S$(xx)ID:$(yy)ID:Message2M ID$(xx):Message3 S$(xx)ID:$(yy)ID:Message3M ID$(xx):OldGapSet S$(xx)ID:$(yy)ID:OldGapSetM ID$(xx):Taper S$(xx)ID:$(yy)ID:TaperM ID$(xx):EncoderSelect S$(xx)ID:$(yy)ID:LinearEncoderUsedM ID$(xx):PositionAccuracy S$(xx)ID:$(yy)ID:PositionAccuracyM ID$(xx):Location S$(xx)ID:$(yy)ID:LocationM ID$(xx):Device S$(xx)ID:$(yy)ID:DeviceM ID$(xx):Version S$(xx)ID:$(yy)ID:$(dd)VersionM Where dd = HPMU, Rev (Revolver), STI (2-Motor ID) ID$(xx):ShClosedTime ID$(xx)(zz):ShClosedTime Where zz = us or ds ID$(xx):MotorSpeed S$(xx)ID:$(yy)ID:MotorSpeedC ID$(xx):GapReturn S$(xx)ID:$(yy)ID:GapReturnM ID$(xx):TaperGapReturn S$(xx)ID:$(yy)ID:TaperGapReturnM ID$(xx):TotalPower S$(xx)ID:$(yy)ID:TotalPowerM ID$(xx):ExpectedPower S$(xx)ID:$(yy)ID:ExpectedPowerM ID$(xx):AccessSecurity S$(xx)ID:$(yy)ID:AccessSecurityC ID$(xx):DeviceLimit S$(xx)ID:$(yy)ID:DeviceLimitM
Removed
The synchronous scanning PVs (those beginning with SS) have been removed. It is unlikely that any beamline was using these PVs.