longin - Long Input

The normal use for the long input record or "longin" record is to retrieve a long integer value of up to 32 bits. Device support routines are provided to support direct interfaces to hardware. In addition, the Soft Channel device module is provided to obtain input via database or channel access links or via dbPutField or dbPutLink requests.

Parameter Fields

The fields in this record fall into the following categories:

  • scan parameters
  • read parameters
  • operator display parameters
  • alarm parameters
  • run-time and simulation mode parameters

Scan Parameters

The long input record has the standard fields for specifying under what circumstances the record will be processed. These fields are listed in Scan Fields. In addition, Scanning Specification explains how these fields are used. Note that I/O event scanning is only supported for those card types that interrupt.


Read Parameters

The device support routines use the INP field to obtain the record's input. For records that obtain their input from devices, the INP field must contain the address of the I/O card, and the DTYP field must specify the proper device support module. Be aware that the address format differs according to the I/O bus used. You can see a list of the device support modules currently supported at the user's local site by using the dbst utility in R3.13.

For soft records, the INP can be a constant, a database link, or a channel access link. The value is read directly into VAL. The Soft Channel device support module is available for longin records. See Address Specification for information on the format of hardware addresses and a database links.


FieldSummaryTypeDCTInitialAccessModifyRec Proc MonitorPP
VALValue FieldLONGNo0YesYesYesYes
INPInput LinkINLINKYes0YesYesNoNo
DTYPDevice TypeDEVCHOICEYes0YesNoNo 


Operator Display Parameters

These parameters are used to present meaningful data to the operator. These fields are used to display the value and other parameters of the long input either textually or graphically.

EGU is a string of up to 16 characters describing the units that the long input measures. It is retrieved by the get_units record support routine.

The HOPR and LOPR fields set the upper and lower display limits for the VAL, HIHI, HIGH, LOW, and LOLO fields. Both the get_graphic_double and get_control_double record support routines retrieve these fields.

See Fields Common to All Record Types for more on the record name (NAME) and description (DESC) fields.


FieldSummaryTypeDCTInitialAccessModifyRec Proc MonitorPP
EGUEngineering UnitsSTRING [16]YesnullYesYesNoNo
HOPRHigh Operating RangeLONGYes0YesYesNoNo
LOPRLow Operating RangeLONGYes0YesYesNoNo
NAMERecord NameSTRING [29]Yes0YesNoNoNo
DESCDescriptionSTRING [29]YesNullYesYesNoNo


Alarm Parameters

The possible alarm conditions for long inputs are the SCAN, READ, and limit alarms. The SCAN and READ alarms are called by the record or device support routines.

The limit alarms are configured by the user in the HIHI, LOLO, HIGH, and LOW fields using numerical values. For each of these fields, there is a corresponding severity field which can be either NO_ALARM, MINOR, or MAJOR. The HYST field can be used to specify a deadband around each limit. See Alarm Specification for a complete explanation of alarms and these fields. Alarm Fields lists other fields related to a alarms that are common to all record types.


FieldSummaryTypeDCTInitialAccessModifyRec Proc MonitorPP
HIHIHihi Alarm LimitLONGYes0YesYesNoYes
HIGHHigh Alarm LimitLONGYes0YesYesNoYes
LOWLow Alarm LimitLONGYes0YesYesNoYes
LOLOLolo Alarm LimitLONGYes0YesYesNoYes
HHSVHihi Alarm SeverityGBLCHOICEYes0YesYesNoYes
HSVHigh Alarm SeverityGBLCHOICEYes0YesYesNoYes
LSVLow Alarm SeverityGBLCHOICEYes0YesYesNoYes
LLSVLolo Alarm SeverityGBLCHOICEYes0YesYesNoYes
HYSTAlarm DeadbandLONGYes0YesYesNoNo


Monitor Parameters

These parameters are used to determine when to send monitors placed on the value field. The monitors are sent when the value field exceeds the last monitored field (see the next section) by the appropriate deadband. If these fields have a value of zero, everytime the value changes, a monitor will be triggered; if they have a value of -1, everytime the record is scanned, monitors are triggered. The ADEL field is used by archive monitors and the MDEL field for all other types of monitors. See Monitor Specification for a complete explanation of monitors.


FieldSummaryTypeDCTInitialAccessModifyRec Proc MonitorPP
ADELArchive DeadbandLONGYes0YesYesNoNo
MDELMonitor, i.e. value change, DeadbandLONGYes0YesYesNoNo


Run-time and Simulation Mode Parameters

The LALM, MLST, and ALST fields are used to implement the hysteresis factors for monitor callbacks. Only if the difference between these fields and the corresponding value field is greater than the appropriate delta (MDEL, ADEL, HYST)--only then are monitors triggered. For instance, only if the difference between VAL and MLST is greater than MDEL are the monitors triggered for VAL.


FieldSummaryTypeDCTInitialAccessModifyRec Proc MonitorPP
LALMLast Alarm Monitor Trigger ValueLONGNo0YesNoNoNo
ALSTLast Archiver Monitor Trigger ValueLONGNo0YesNoNoNo
MLSTLast Value Change Monitor Trigger ValueLONGNo0YesNoNoNo

The following fields are used to operate the long input in the simulation mode. See Fields Common to Many Record Types for more information on these fields.


FieldSummaryTypeDCTInitialAccessModifyRec Proc MonitorPP
SIOLSimulation Value LocationINLINKYes0YesYesNoNo
SVALSimulation ValueLONGNo0YesYesNoNo
SIMLSimulation Mode LocationINLINKYes0YesYesNoNo
SIMMSimulation ModeGBLCHOICENo0YesYesNoNo
SIMSSimulation Mode Alarm SeverityGBLCHOICEYes0YesYesNoNo


Record Support

Record Support Routines

init_record

This routine initializes SIMM with the value of SIML if SIML type is CONSTANT link or creates a channel access link if SIML type is PV_LINK. SVAL is likewise initialized if SIOL is CONSTANT or PV_LINK.

This routine next checks to see that device support is available and a device support read routine is defined. If either does not exist, an error message is issued and processing is terminated.

If device support includes init_record, it is called.

process

See next section.

get_value

Fills in the values of struct valueDes so that they refer to VAL.

get_units

Retrieves EGU.

get_graphic_double

Sets the upper display and lower display limits for a field. If the field is VAL, HIHI, HIGH, LOW, or LOLO, the limits are set to HOPR and LOPR, else if the field has upper and lower limits defined they will be used, else the upper and lower maximum values for the field type will be used.

get_control_double

Sets the upper control and the lower control limits for a field. If the field is VAL, HIHI, HIGH, LOW, or LOLO, the limits are set to HOPR and LOPR, else if the field has upper and lower limits defined they will be used, else the upper and lower maximum values for the field type will be used.

get_alarm_double

Sets the following values:

 upper_alarm_limit = HIHI
 upper_warning_limit = HIGH
 lower_warning_limit = LOW
 lower_alarm_limit = LOLO


Record Processing

Routine process implements the following algorithm:


  1. Check to see that the appropriate device support module exists. If it doesn't, an error message is issued and processing is terminated with the PACT field still set to TRUE. This ensures that processes will no longer be called for this record. Thus error storms will not occur.
  2. readValue is called. See Input Records for more information.
  3. If PACT has been changed to TRUE, the device support read routine has started but has not completed reading a new input value. In this case, the processing routine merely returns, leaving PACT TRUE.
  4. Check alarms. This routine checks to see if the new VAL causes the alarm status and severity to change. If so, NSEV, NSTA and LALM are set. It also honors the alarm hysteresis factor (HYST). Thus the value must change by more than HYST before the alarm status and severity is lowered.
  5. Check to see if monitors should be invoked:
    • Alarm monitors are invoked if the alarm status or severity has changed.
    • Archive and value change monitors are invoked if ADEL and MDEL conditions are met.
    • NSEV and NSTA are reset to 0.
  6. Scan forward link if necessary, set PACT FALSE, and return.


Device Support

Fields Of Interest To Device Support

Each long input record must have an associated set of device support routines. The primary responsibility of the device support routines is to obtain a new input value whenever read_longin is called. The device support routines are primarily interested in the following fields:


NameSummaryDescription
PACTProcessing ActiveSee Fields Common to All Record Types for an explanation of these fields.
DPVTDevice Private
UDFVAL Undefined
NSEVNew Alarm Severity
NSTANew Alarm Status
VALValue FieldThis field is set by device support routines.
INPInput LinkThis field is used by the device support routines to locate its input.


Device Support routines

Device support consists of the following routines:

report

report(FILE fp, paddr)

Not currently used.

init

init()

This routine is called once during IOC initialization.

init_record

init_record(precord)

This routine is optional. If provided, it is called by the record support init_record routine.

get_ioint_info

get_ioint_info(int cmd,struct dbCommon *precord,IOSCANPVT *ppvt)

This routine is called by the ioEventScan system each time the record is added or deleted from an I/O event scan list. cmd has the value (0,1) if the record is being (added to, deleted from) an I/O event list. It must be provided for any device type that can use the ioEvent scanner.

read_longin

read_longin(precord)

This routine must provide a new input value. It returns the following values:

  • 0: Success. A new value is placed in VAL.
  • Other: Error.

Device Support For Soft Records

The Soft Channel device support module places a value directly in VAL.

If the INP link type is constant, then the constant value is stored into VAL by init_record, and UDF is set to FALSE. If the INP link type is PV_LINK, then dbCaAddInlink is called by init_record.

read_longin calls recGblGetLinkValue to read the current value of VAL. See Soft Input for more information

If the return status of recGblGetLinkValue is zero then read_longin sets UDF to FALSE. read_longin returns the status of recGblGetLinkValue.




EPICS Record Reference Manual - 19 MAY 1998