Difference between revisions of "RRM 3-14 Calculation"
m (→Alarm Parameters: Fixed typo.) |
|||
Line 227: | Line 227: | ||
The following alarm parameters which are configured by the user define the limit alarms for the VAL field and the severity corresponding to those conditions. | The following alarm parameters which are configured by the user define the limit alarms for the VAL field and the severity corresponding to those conditions. | ||
The HYST field defines an alarm deadband for each limit. See [[RRM 3-14 Concepts#Alarm Specification|Alarm Specification]] for a complete explanation of alarms and these fields. [[RRM 3-14 dbCommon#Alarm Fields|Alarm Fields]] lists other fields related to | The HYST field defines an alarm deadband for each limit. See [[RRM 3-14 Concepts#Alarm Specification|Alarm Specification]] for a complete explanation of alarms and these fields. [[RRM 3-14 dbCommon#Alarm Fields|Alarm Fields]] lists other fields related to alarms that are common to all record types. | ||
Line 242: | Line 242: | ||
<TD>HYST<TD>Alarm Deadband<TD>DOUBLE<TD>Yes<TD>0<TD>Yes<TD>Yes<TD>No<TD>No | <TD>HYST<TD>Alarm Deadband<TD>DOUBLE<TD>Yes<TD>0<TD>Yes<TD>Yes<TD>No<TD>No | ||
</TABLE> | </TABLE> | ||
=== Monitor Parameters === | === Monitor Parameters === |
Revision as of 17:20, 18 December 2009
Calc - Calculation
The calculation or "Calc" record is used to perform algebraic, relational, and logical operations on values retrieved from other records. The result of its operations can then be accessed by another record so that it can be used.
Parameter Fields
The fields in this record fall into these categories:
- scan parameters
- read parameters
- expression parameters
- operator display parameters
- alarm parameters
- monitor parameters
- run-time parameters
Scan Parameters
The Calc record has the standard fields for specifying under what circumstances the record will be processed. These fields are listed in Scan Fields. In addition, Scanning Specification explains how these fields are used. Since the Calc record supports no direct interfaces to hardware, it cannot be scanned on I/O interrupt, so its SCAN field cannot be I/O Intr
.
Read Parameters
The read parameters for the Calc record consist of 12 input links INPA, INPB, ... INPL. The fields can be database links, channel access links, or constants. If they are links, they must specify another record's field or a channel access link. If they are constants, they will be initialized with the value they are configured with and can be changed via dbPuts
. They cannot be hardware addresses.
See Address Specification for information on how to specify database links.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor |
---|---|---|---|---|---|---|---|
INPA | Input Link A | INLINK | Yes | 0 | No | No | N/A |
INPB | Input Link B | INLINK | Yes | 0 | No | No | N/A |
INPC | Input Link C | INLINK | Yes | 0 | No | No | N/A |
INPD | Input Link D | INLINK | Yes | 0 | No | No | N/A |
INPE | Input Link E | INLINK | Yes | 0 | No | No | N/A |
INPF | Input Link F | INLINK | Yes | 0 | No | No | N/A |
INPG | Input Link G | INLINK | Yes | 0 | No | No | N/A |
INPH | Input Link H | INLINK | Yes | 0 | No | No | N/A |
INPI | Input Link I | INLINK | Yes | 0 | No | No | N/A |
INPJ | Input Link J | INLINK | Yes | 0 | No | No | N/A |
INPK | Input Link K | INLINK | Yes | 0 | No | No | N/A |
INPL | Input Link L | INLINK | Yes | 0 | No | No | N/A |
Expression
At the core of the Calc record lie the CALC and RPCL fields. The CALC field contains the infix expression which the record routine will use when it processes the record. The resulting value is placed in the VAL field and can be accessed from there. The CALC expression is actually converted to opcode and stored as in Reverse Polish Notation in the RPCL field. It is this expression which is actually used to calculate VAL. The Reverse Polish expression is evaluated more efficiently during run-time than an infix expression. CALC can be changed at run-time, and a special record routine calls a function to convert it to Reverse Polish Notation.
The range of expressions supported by the calculation record are separated into operands, algebraic operators, trigonometric operators, relational operators, logical operators, parentheses and commas, and the question mark or '?:' operator. The expression can consist of any of these operators, as well as any of the values from the input links which are the operands.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor | PP |
---|---|---|---|---|---|---|---|---|
CALC | Calculation | DBF_STRING | Yes | 0 | Yes | Yes | Yes | Yes |
RPCL | Reverse Polish | DBF_NOACCESS | No | 0 | No | No | N/A | No |
Operands
The expression uses the values retrieved from the INPx links as operands, though constants can be used as operands too. These values retrieved from the input links are stored in the A-L fields. The values to be used in the expression are simply referenced by the field letter. For instance, the value obtained from the INPA link is stored in the field A, and the value obtained from INPB is stored in field B. The field names can be included in the expression which will operate on their respective values, as in A+B. Also, the RNDM unary function can be included as an operand in the expression in order to generate a random number between 0 and 1.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor | PP |
---|---|---|---|---|---|---|---|---|
A | Input Value A | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
B | Input Value B | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
C | Input Value C | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
D | Input Value D | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
E | Input Value E | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
F | Input Value F | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
G | Input Value G | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
H | Input Value H | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
I | Input Value I | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
J | Input Value J | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
K | Input Value K | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
L | Input Value L | DOUBLE | No | 0 | Yes | Yes/No | Yes | Yes |
Algebraic Operators
- ABS: Absolute value (unary)
- SQR: Square root (unary)
- MIN: Minimum (binary function)
- MAX: Maximum (binary function)
- CEIL: Ceiling (unary)
- FLOOR: Floor (unary)
- LOG: Log base 10 (unary)
- LOGE: Natural log (unary)
- EXP: Exponential function (unary)
- ^: Exponential (binary)
- ** : Exponential (binary)
- + : Addition (binary)
- - : Subtraction (binary)
- * : Multiplication (binary)
- / : Division (binary)
- % : Modulo (binary)
- NOT: Negate (unary)
Trigonometric Operators
- SIN: Sine
- SINH: Hyperbolic sine
- ASIN: Arc sine
- COS: Cosine
- COSH: Hyperbolic cosine
- ACOS: Arc cosine
- TAN: Tangent
- TANH: Hyperbolic tangent
- ATAN: Arc tangent
Relational Operators
- >= : Greater than or equal to
- > : Greater than
- <= : Less than or equal to
- <: Less than
- # : Not equal to
- = : Equal to
Logical Operators
- && : And
- || : Or
- ! : Not
Bitwise Operators
- | : Bitwise Or
- & : Bitwise And
- OR : Bitwise Or
- AND: Bitwise And
- XOR: Bitwise Exclusive Or
- ~ : One's Complement
- << : Left shift
- >> : Right shift
Parentheses and Comma
The open and close parentheses are supported. Nested parenthesis are supported.
The comma is supported when used to separate the arguments of a binary function.
Conditional Expression
The C language's question mark operator is supported. The format is:
(condition)? True result : False result
Expression Examples
Algebraic
A + B + 10
- Result is A + B
Relational
(A + B) < (C + D)
- Result is 1 if (A+B) < (C+D)
- Result is 0 if (A+B) >= (C+D)
Question Mark
(A+B)<(C+D)?E:F+L+10
- Result is E if (A+B) < (C+D)
- Result is F+L+10 if (A+B) >= (C+D)
(A+B)<(C+D)?E
- Result is E if (A+B) < (C+D)
- Result is unchanged if (A+B) >= (C+D)
Logical
A&B
- Causes the following to occur:
- Convert A to integer
- Convert B to integer
- Bit-wise And A and B
- Convert result to floating point
Operator Display Parameters
These parameters are used to present meaningful data to the operator. These fields are used to display VAL and the other parameters of the calculation record either textually or graphically.
The EGU field contains a string of up to 16 characters which is supplied by the user and which describes the values being operated upon. The string is retrieved whenever the routine get_units
is called. The EGU string is solely for an operator's sake and does not have to be used.
The HOPR and LOPR fields only refer to the limits of the VAL, HIHI, HIGH, LOW, and LOLO fields. PREC controls the precision of the VAL field.
See Fields Common to All Record Types for more on the record name (NAME) and description (DESC) fields.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor | PP |
---|---|---|---|---|---|---|---|---|
EGU | Engineering Units | STRING [16] | Yes | Null | Yes | Yes | No | No |
PREC | Display Precision | SHORT | Yes | 0 | Yes | Yes | No | No |
HOPR | High Operating Range | FLOAT | Yes | 0 | Yes | Yes | No | No |
LOPR | Low Operating Range | FLOAT | Yes | 0 | Yes | Yes | No | No |
NAME | Record Name | STRING [29] | Yes | 0 | Yes | No | No | No |
DESC | Description | STRING [29] | Yes | Null | Yes | Yes | No | No |
Alarm Parameters
The possible alarm conditions for the Calc record are the SCAN, READ, Calculation, and limit alarms. The SCAN and READ alarms are called by the record support routines. The Calculation alarm is called by the record processing routine when the CALC expression is an invalid one, upon which an error message is generated.
The following alarm parameters which are configured by the user define the limit alarms for the VAL field and the severity corresponding to those conditions.
The HYST field defines an alarm deadband for each limit. See Alarm Specification for a complete explanation of alarms and these fields. Alarm Fields lists other fields related to alarms that are common to all record types.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor | PP |
---|---|---|---|---|---|---|---|---|
HIHI | Hihi Alarm Limit | FLOAT | Yes | 0 | Yes | Yes | No | Yes |
HIGH | High Alarm Limit | FLOAT | Yes | 0 | Yes | Yes | No | Yes |
LOW | Low Alarm Limit | FLOAT | Yes | 0 | Yes | Yes | No | Yes |
LOLO | Lolo Alarm Limit | FLOAT | Yes | 0 | Yes | Yes | No | Yes |
HHSV | Severity for a Hihi Alarm | GBLCHOICE | Yes | 0 | Yes | Yes | No | Yes |
HSV | Severity for a High Alarm | GBLCHOICE | Yes | 0 | Yes | Yes | No | Yes |
LSV | Severity for a Low Alarm | GBLCHOICE | Yes | 0 | Yes | Yes | No | Yes |
LLSV | Severity for a Lolo Alarm | GBLCHOICE | Yes | 0 | Yes | Yes | No | Yes |
HYST | Alarm Deadband | DOUBLE | Yes | 0 | Yes | Yes | No | No |
Monitor Parameters
These parameters are used to determine when to send monitors for the value fields. The monitors are sent when the value field exceeds the last monitored field by the appropriate deadband, the ADEL for archiver monitors and the MDEL field for all other types of monitors. If these fields have a value of zero, everytime the value changes, monitors are triggered; if they have a value of -1, everytime the record is scanned, monitors are triggered. See Monitor Specification for a complete explanation of monitors.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor | PP |
---|---|---|---|---|---|---|---|---|
ADEL | Archive Deadband | DOUBLE | Yes | 0 | Yes | Yes | No | No |
MDEL | Monitor, i.e. value change, Deadband | DOUBLE | Yes | 0 | Yes | Yes | No | No |
Run-time Parameters
These fields are not configurable using a configuration too and none are modifiable at run-time. They are used to process the record.
The LALM field is used to implement the hysteresis factor for the alarm limits.
The LA-LL fields are used to decide when to trigger monitors for the corresponding fields. For instance, if LA does not equal the value for A, monitors for A are triggered. The MLST and MLST fields are used in the same manner for the VAL field.
Field | Summary | Type | DCT | Initial | Access | Modify | Rec Proc Monitor | PP |
---|---|---|---|---|---|---|---|---|
LALM | Last Alarmed Value | DOUBLE | No | 0 | Yes | No | No | No |
ALST | Archive Last Value | DOUBLE | No | 0 | Yes | No | No | No |
MLST | Monitor Last Value | DOUBLE | No | 0 | Yes | No | No | No |
LA | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LB | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LC | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LD | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LE | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LF | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LG | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LH | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LI | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LJ | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LK | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
LL | Previous Input Value for A | DOUBLE | No | 0 | Yes | No | No | No |
Record Support
Record Support Routines
init_record
For each constant input link, the corresponding value field is initialized with the constant value if the input link is CONSTANT or a channel access link is created if the input link is PV_LINK.
A routine postfix is called to convert the infix expression in CALC to reverse polish notation. The result is stored in RPCL.
process
See next section.
special
This is called if CALC is changed. special calls postfix.
get_value
Fills in the values of struct valueDes so that they refer to VAL.
get_units
Retrieves EGU.
get_precision
Retrieves PREC.
get_graphic_double
Sets the upper display and lower display limits for a field. If the field is VAL, HIHI, HIGH, LOW, or LOLO, the limits are set to HOPR and LOPR, else if the field has upper and lower limits defined they will be used, else the upper and lower maximum values for the field type will be used.
get_control_double
Sets the upper control and the lower control limits for a field. If the field is VAL, HIHI, HIGH, LOW, or LOLO, the limits are set to HOPR and LOPR, else if the field has upper and lower limits defined they will be used, else the upper and lower maximum values for the field type will be used.
get_alarm_double
Sets the following values:
upper_alarm_limit = HIHI upper_warning_limit = HIGH lower_warning_limit = LOW lower_alarm_limit = LOLO
Record Processing
Routine process implements the following algorithm:
- Fetch all arguments.
- Call routine calcPerform, which calculates VAL from the postfix version of the expression given in CALC. If calcPerform returns success UDF is set to FALSE.
- Check alarms. This routine checks to see if the new VAL causes the alarm status and severity to change. If so, NSEV, NSTA and LALM are set. It also honors the alarm hysteresis factor (HYST). Thus the value must change by at least HYST before the alarm status and severity changes.
- Check to see if monitors should be invoked.
- Alarm monitors are invoked if the alarm status or severity has changed.
- Archive and value change monitors are invoked if ADEL and MDEL conditions are met.
- Monitors for A-L are checked whenever other monitors are invoked.
- NSEV and NSTA are reset to 0.
- Scan forward link if necessary, set PACT FALSE, and return.
EPICS Record Reference Manual - 19 MAY 1998